Unit-tested 2026 NEC (Texas Article 120) and 2023 NEC (Article 220) exam math

Dwelling general load (120.41 / Table 120.45)

2026 NEC 120.41 uses 2 VA/sq ft for feeders/services while 120.13 keeps 3 VA/sq ft for branch-circuit counts.

  • Unit lighting load2 VA / sq ft
  • Gross combined VA10,100 VA
  • Net demand load5,485 VA
  • Min 15A lighting circuits (3 VA/sq ft)5 circuits

Single electric range (Table 120.55)

Col. B (<=8.75 kW = 80%), Col. C (8.75 to 12 kW = 8 kW), and Note 1 (+5% per kW or major fraction over 12 kW).

  • Major fraction over 12 kW4 kW
  • Note 1 increase+20%
  • Maximum demand load9.6 kW (9,600 VA)

Box fill with 5+ grounds (314.16(B)(5))

First 4 EGCs count as 1.0 allowance; each additional EGC beyond 4 adds 0.25 allowance (2023 and 2026 NEC).

  • EGC allowance (with clamps = 1)1.25 allowances
  • Total volume allowances10.25
  • Minimum required box volume23.0625 cu. in.

Three-phase motor sizing (Table 430.250)

430.6(A)(1) mandates Table 430.250 FLC for conductors (125%) and inverse-time breakers (250%).

  • Table 430.250 FLC34 A
  • Min conductor ampacity (430.22)42.5 A
  • Max inverse-time breaker (430.52)90 A

Dwelling optional load (120.82(B) 8 kVA tier)

2026 NEC 120.82(B) takes the first 8,000 VA at 100% plus 40% of the remainder.

  • 100% first-tier cap8,000 VA
  • Remainder @ 40%18,500 VA
  • Net optional general load26,500 VA

EMT conduit fill (Ch. 9 Table 1 31% 2-wire rule)

1 conductor = 53% max fill; 2 conductors = 31% max fill; 3 or more conductors = 40% max fill.

  • Governing Ch. 9 Table 1 fill limit31%
  • Total THHN conductor area0.4446 sq. in.
  • Minimum permitted EMT trade size1-1/4" EMT